6. PARAMETER DESCRIPTION

[G13: High High Alarm]

High-high alarm setting

This parameter sets the high-high limit (HH) alarm
value, and this is done using a % value of the maxi-
mum span.
᭹ A setting value of 110% indicates that the alarm is

disabled.

NOTE

Setting of -110% or 110% results in the corre-
sponding function being disabled; accordingly,
settings can be combined to implement only high
alarms or low alarms, etc.

Output Example 1

The high-high alarm (HH) is set to 90% or more of the
flow rate span; the low-low alarm (LL), to 20% or less;
the high alarm (H), to 80% or more; and the low alarm
(L), to 30% or less.

Settings are:

G10: Low Alarm

= 30%

G11: High Alarm

= 80%

G12: Low Low Alarm

= 20%

G13: High High Alarm

= 90%

0

Time (t)

H

L

HH

SO1

SO2

LL

HH

AL

LL

High High Alarm

High Alarm

Instantaneous flow rate

Low Alarm

Low Low Alarm

20

30

50

80

90

100

[%]

Select “H/L Alarm” for F10: SO1 Function
Select “HH/LL Alarm” for F11: SO2 Function
Select “Closed (On) Act” for F14: SO1/2 Active Mode
Select “Open (Off) Act” for G20: Alm Out Act Mode
Select “Yes” for G33: Alm-HH/LL

F0610.EPS

Output Example 2

The high alarm (H) is set to 80% or more of the flow
rate span; the low-low alarm (LL), to 20% or less.

Settings are:

G10: Low Alarm

= -110%

G11: High Alarm

= 80%

G12: Low Low Alarm

= 20%

G13: High High Alarm

= 110%

0

Time (t)

H

SO1

SO2

LL

AL

LL

Instantaneous flow rate

20

50

80

100

[%]

F0611.EPS

L Alarm set to
-110% indicates
that the alarm is
disabled.

High Alarm

Low Low Alarm

HH Alarm set to 110% indicates
that the alarm is disabled.

Select “H/L Alarm” for F10: SO1 Function
Select “HH/LL Alarm” for F11: SO2 Function
Select “Closed (On) Act” for F14: SO1/2 Active Mode
Select “Open (Off) Act” for G20: Alm Out Act Mode
Select “Yes” for G33: Alm-HH/LL