2 alarm selection, Alarm selection -36 – APC AXFA11G User Manual

Page 64

Advertising
background image

IM 01E20C01-01E

6-36

6. PARAMETER DESCRIPTION

6.5.2

Alarm Selection

The display and output differs depending on the alarm
levels. Certain types of alarm may or may not be
recognized as alarms, according to the settings of
certain parameters. The parameters that are relevant to
this function as follows.

[G20: Alm Out Act Mode]

Setting of the active

mode for the alarm output

[G21: 4-20mA Alarm Out]

Setting of the current

output during an alarm occurring.

[G30: Alm-Setting]

Alarm recognition of “Setting

Alarm”

[G31: Alm-Sig Over]

Alarm recognition of “Signal

Overflow Alarm”

[G32: Alm-Emp Pipe]

Alarm recognition of “Empty

Pipe alarm”

[G33: Alm-HH/LL]

Alarm recognition of “HH/LL

Alarm” (Refer to the descriptions of

G12

and

G13

for

more details regarding HH and LL alarms.)

[G34: Alm-Adhesion]

Alarm recognition of “Adhe-

sion Alarm”

[G41: Alm Record1]

Alarm record1

[G43: Alm Record2]

Alarm record2

[G45: Alm Record3]

Alarm record3

[G47: Alm Record4]

Alarm record4

(1) Display and output condition for system alarms

Alarm description

Alarm

output

4-20 mA

output

Totali-
zation Pulse

Display unit

Alarm

record

Normal

Normal

Normal Normal Display Mode

No

Closed

(On)

␮P Fault
EEPROM Fault

A/D(H) Fault

A/D(L) Fault

A/D(Z) Fault

Coil Open

EEPROM Dflt

Microprocessor(CPU)failure

EEPROM failure

A/D converter failure

Flowtube coil is open-circuit

EEPROM default values

Open

(Off)

Fixed

(G21 selection)

Stopped Stopped

Recorded

Alarm Mode

(display of system

alarm message)

Open

(Off)

0mA or

25mA

Stopped Indetermination

10

11

12

13

14

15

16

T0648.EPS

Note: • Operations are performed in accordance with above table, when “Open (Off) Act” is set for

G20: Alm

Out Act Mode

.

• 4-20 mA output upon the occurrence of an alarm will be fixed at the value selected with

G21: 4-20mA

Alarm Out

.

*The output value is performed in accordance with the setting of the burnout switch. For information about

this switch, see Section 10.2.1.

Indeter-
mination

Indeter-
mination

(*)

(2) Display and output condition for process alarms

Alarm

description

Selection

(parameter

number)

Alarm

output

4-20 mA

output

Totali-
zation

Pulse

output

Display

unit

Alarm

record

30

31

32

33

Sig Overflow

Empty Pipe

HH/LL Alm

Adhesion Alm

Input signal error

Flowtube is not
filled with fluid

HH/LL Alarm

Electrode
adhesion alarm

T0649.EPS

Alarm Mode

(Message)

Alarm Mode

(Message)

Alarm Mode

(Message)

Alarm Mode

(Message)

Display Mode

Display Mode

Display Mode

Display Mode

Fixed

Continu-

ous (*)

Continu-

ous (*)

Continu-

ous (*)

Fixed

Stopped

Continu-

ous (*)

Continu-

ous (*)

Continu-

ous (*)

Stopped

Stopped

Continu-

ous (*)

Continu-

ous (*)

Continu-

ous (*)

Stopped

Normal

operation

Normal

operation

Normal

operation

Fixed

Stopped Stopped

Recorded

No

Recorded

No

No

Recorded

No

Open

(Off)

Closed

(On)

Open

(Off)

Closed

(On)

Open

(Off)

Closed

(On)

Open

(Off)

Closed

(On)

YES

(G31)

NO

(G31)

YES

(G32)

NO

(G32)

YES

(G33)

NO

(G33)

YES

(G34)

NO

(G34)

Note: • Operations are performed in accordance with above table, when “Open (Off) Act” is set for

G20: Alm

Out Act Mode

.

• 4-20 mA output upon the occurrence of an alarm will be fixed at the value selected with

G21: 4-20mA

Alarm Out

.

*: Although outputs are continuous, output values are not guaranteed.