6. PARAMETER DESCRIPTION

[C45: Density Unit]

Setting of the density units for

mass flow rate
This parameter selects the units for density as required
when making settings using

C46: Mass Density

.

[C46: Mass Density]

Setting of the density for mass

flow rate
This parameter is necessary in situations where t, kg, g,
klb or lb has been selected as the mass unit in

B21/

C40: Base Flow Unit

. If a mass unit is selected in

B21/C40: Base Flow Unit

and a value of 0 is set for

this parameter, the setting alarm “

57: Dens Set Err

will be displayed. In such a case, ensure that the
density is set correctly.

[C47: User Span Select]

Selection of the use of

special flow rate units.
This parameter selects whether or not special units are
used for instantaneous flow rate. Actual setting of these
units is carried out using

C48: Flow User Unit

and

C49: Flow User Span

.

[C48: Flow User Unit]

Setting of the special flow

rate units
This parameter is used to select the special units (up to
maximum of 8 characters in length). These units are
displayed when instantaneous flow rate is selected in
the Display Mode, and they are displayed for

A20:

FLOW RATE

when BRAIN communication is being

carried out.

[C49: Flow User Span]

Setting of the special flow

rate span
This parameter sets the special flow rate span to be
displayed for 100% output in the maximum range.

NOTE

Example :

To set the special flow rate span to
100 dl/s
Since 100 dl (deci-liter)=10 l (liter),
“l (Liter)” is set for B21/C40: Base
Flow Unit
,
“/s” is set for B22/C41: Base Time
Unit
,
“10” is set for B23/C42: Flow
Span
,
“Yes” is set for C47: User Span
Select
,
“dl/s” is set for C48: Flow User
Unit
,
“100” is set for C49: Flow User

Span.
“100 dl/s” is indicated for 100%
output in the Display Mode.

(3) Menu D: Total Setting items

Menu D contains parameters that are relevant to
totalization function settings.

[D10: Total Unit]

Setting of units for totalization

scale

Refer to the description of parameter

B30

.

[D11: Total Scale]

Setting of the totalization scale

Refer to the description of parameter

B31

.

[D12: Total Decimal Pnt]

Setting of the decimal

point position for the totalization display
This parameter sets the position of the decimal point
for totalization display in terms of the number of digits.
Except in cases where 0 is selected, the totalized units
are not displayed.

Example: When totalized value is 12345678 m

3

T0619.EPS

Item

Totalization display

0

1

2

3

4

5

6

7

12345678 m

3

1234567.8

123456.78

12345.678

1234.5678

123.45678

12.345678

1.2345678

[D13: Total Low Cut]

Setting of the totalization stop

range
This parameter allows the settings to be made that
prevent totalization when the flow rate is at or below
the low-cut setting value. In cases where there are
multiple ranges or forward/reverse ranges, low cut is
carried out at the setting value for the smallest span
(i.e., an integer between 0 and 10%).
Example: When the first range = 10 m

3

/h, the second

range = 100 m

3

/h, and the Total Low Cut =

3%, no totalization is carried out at flow
rates of 0.3 m

3

/h or lower.