4. Commissioning

4-16

Festo P.BE-SPC11-SYS-EN en 1406e

4.2.5 Set parameters

At the factory, all the parameters are zero (status at delivery).
When the power supply is switched on, the SPC11 in this case
expects entry of the parameters. In preparation for commis-
sioning, the parameters can be set “in the office” without
setting up the drive. This simplifies the commissioning of
large series in production.

Set the parameters without drive (in the office) as follows:

Warning
Incorrectly set parameters can damage the fixed stops and
the drive.

Be very careful when setting the parameters.

The right amplification and cushioning stages and the system
parameter for your drive can be found in the drive-specific
supplement. The values specified here are examples. Instead,
enter the values valid for setting up your drive.

1. Switch on the operating voltage for the SPC11.

The SPC11 will then show briefly the version number of
the internal firmware.
The SPC11 then expects the amplification stage to be
entered. The display shows the letter A (Amplification
stage). The figures indicate the stage (here 0).

(A.00)

2. Set amplification stage with +/-, e.g. 02.

(A.02)

3. Hold the Enter key pressed down for more than

2 seconds (

> 2 s).

The value will then be transferred to the SPC11 and the