4. Commissioning

4-21

Festo P.BE-SPC11-SYS-EN en 1406e

4.2.6 Changing parameters

Please note
The option parameter o can be changed without a new
teach procedure being necessary. After the parameters A,
C, S, L or r are changed, the teach procedure must be per-
formed again.

If necessary, the set parameters can be modified, e.g. in order
to correct entry errors or to optimise positioning behaviour.
This can be carried out in one of the following ways:

Possibilities

Description

Activate modification
mode

In this mode the set parameter values are
retained and can be modified or trans-
ferred. Taught intermediate positions are
retained.

Create status as at
delivery

All parameter values are then set to 0.
Taught intermediate positions are deleted.

Activate modification mode

Condition

The measuring system must be connected. There must be a
0-signal at input Remote (I8). The drive must be at a stand-
still.

Caution
When the modification mode is activated, the valve slide
assumes the mid-position. During positioning the mass
can therefore move uncushioned into an end position.

Make sure that the drive is standing still before you acti-
vate the modification mode.