Bryant Gas Furance 315AAV User Manual

Page 12

Advertising
background image

12

PLENUM

OPENING

C

A

B

D

FLOOR

OPENING

A96283

Fig. 11 -- Floor and Plenum Opening Dimensions

Roll--Out Protection
Provide a minimum 17--3/4--in. X 22--in. (451 X 559 mm) piece
of sheet metal for flame roll--out protection in front of burner area

for furnaces closer than 12--in. (305 mm) above the combustible

deck or suspended furnaces closer than 12--in. (305 mm) to joists.
The sheet metal MUST extend underneath the furnace casing by

1--in. (25 mm)with the door removed.
The bottom closure panel on furnaces of widths 17--1/2--in. (445

mm) and larger may be used for flame roll--out protection when

bottom of furnace is used for return air connection. See Fig. 17
for proper orientation of roll--out shield.
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in

bottom return--air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel,

perform the following:

1. Tilt or raise furnace and remove two screws holding bot-

tom filler panel. (See Fig. 9.)

2. Rotate bottom filler panel downward to release holding

tabs.

3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.

Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in

bottom return--air opening. This panel MUST be in place when
side return air inlet(s) are used without a bottom return air inlet.

DOWNFLOW

SUBBASE

SHEET METAL

PLENUM

FLOOR

OPENING

FURNACE

(OR COIL CASING

WHEN USED)

COMBUSTIBLE

FLOORING

A96285

Fig. 12 -- Furnace, Plenum, and Subbase Installed on a

Combustible Floor

APPROVED

COIL ASSEMBLY

OR

COIL BOX

FURNACE

SHEET METAL

PLENUM

FLOOR

OPENING

COMBUSTIBLE

FLOORING

A08556

Fig. 13 -- Furnace, Plenum, and Coil Assembly or Coil Box

Installed on a Combustible Floor

Not all horizontal furnaces are approved for side return air
connections (See Fig. 20.)

315AA

V