Table 14 – Orifice Size and Manifold Pressure (In. W.C.) for Gas Input Rate

(Tabulated Data Based on 22,000 Btuh High--Heat/14,500 Btuh for Low--Heat per Burner, Derated 4 Percent for Each 1000 Ft.

(305 M) Above Sea Level)

ALTITUDE RANGE

FT. (M)

AVG. GAS

HEAT VALUE

(BTUH/CU FT.)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

USA

0 to

2000

(0 to 610)

900

42

3.5/1.5

42

3.6/1.6

42

3.7/1.6

41

3.5/1.5

925

42

3.3/1.4

42

3.4/1.5

42

3.5/1.5

42

3.7/1.6

950

43

3.8/1.7

42

3.3/1.4

42

3.4/1.5

42

3.5/1.5

975

43

3.6/1.6

43

3.8/1.6

42

3.2/1.4

42

3.3/1.4

1000

43

3.5/1.5

43

3.6/1.6

43

3.7/1.6

43

3.8/1.7

1025

43

3.3/1.4

43

3.4/1.5

43

3.5/1.5

43

3.6/1.6

1050

44

3.6/1.6

43

3.2/1.4

43

3.4/1.5

43

3.5/1.5

1075

44

3.4/1.5

44

3.5/1.5

43

3.2/1.4

43

3.3/1.4

1100

44

3.3/1.4

44

3.4/1.5

44

3.5/1.5

43

3.2/1.4

ALTITUDE RANGE

FT. (M)

AVG. GAS

HEAT VALUE

(BTUH/CU FT.)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

USA

2001 to

3000 (610

to 914)

800

42

3.4/1.5

42

3.5/1.5

42

3.6/1.6

42

3.7/1.6

825

42

3.2/1.4

42

3.3/1.4

42

3.4/1.5

42

3.5/1.5

850

43

3.7/1.6

43

3.8/1.6

42

3.2/1.4

42

3.3/1.4

875

43

3.5/1.5

43

3.6/1.6

43

3.7/1.6

43

3.8/1.7

900

43

3.3/1.4

43

3.4/1.5

43

3.5/1.5

43

3.6/1.6

925

44

3.5/1.5

43

3.2/1.4

43

3.3/1.4

43

3.4/1.5

950

44

3.4/1.5

44

3.5/1.5

44

3.6/1.6

43

3.2/1.4

975

44

3.2/1.4

44

3.3/1.4

44

3.4/1.5

44

3.5/1.5

1000

45

3.7/1.6

45

3.8/1.7

44

3.2/1.4

44

3.4/1.5

ALTITUDE RANGE

FT. (M)

AVG. GAS

HEAT VALUE

(BTUH/CU FT.)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

USA

3001 to

4000

(914 to

1219)

775

42

3.2/1.4

42

3.3/1.4

42

3.4/1.5

42

3.5/1.5

800

43

3.6/1.6

43

3.8/1.6

42

3.2/1.4

42

3.3/1.4

825

43

3.4/1.5

43

3.5/1.5

43

3.7/1.6

43

3.8/1.6

850

43

3.2/1.4

43

3.3/1.4

43

3.4/1.5

43

3.6/1.5

875

44

3.5/1.5

44

3.6/1.6

43

3.3/1.4

43

3.4/1.5

900

44

3.3/1.4

44

3.4/1.5

44

3.5/1.5

43

3.2/1.4

925

45

3.8/1.6

44

3.2/1.4

44

3.3/1.5

44

3.4/1.5

950

46

3.8/1.6

45

3.7/1.6

45

3.8/1.7

44

3.3/1.4

ALTITUDE RANGE

FT. (M)

SPECIFIC GRAVITY OF NATURAL GAS

AVG. GAS

HEAT VALUE

(BTUH/CU FT.)

0.58

0.60

0.62

0.64

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

Orifice

No.

Manifold

Pressure

High/Low

USA

4001 to

5000

(1219 to

1524)

750

43

3.6/1.6

43

3.8/1.6

42

3.2/1.4

42

3.3/1.4

775

43

3.4/1.5

43

3.5/1.5

43

3.6/1.6

43

3.8/1.6

800

43

3.2/1.4

43

3.3/1.4

43

3.4/1.5

43

3.5/1.5

825

44

3.4/1.5

44

3.6/1.5

43

3.2/1.4

43

3.3/1.4

850

44

3.2/1.4

44

3.4/1.5

44

3.5/1.5

44

3.6/1.6

875

45

3.7/1.6

45

3.8/1.7

44

3.3/1.4

44

3.4/1.5

900

46

3.7/1.6

46

3.8/1.7

45

3.7/1.6

44

3.2/1.4

925

46

3.5/1.5

46

3.6/1.6

46

3.7/1.6

46

3.8/1.7

* Orifice numbers 43 are factory installed