Caution – Bryant Gas Furance 315AAV User Manual

Page 30

Advertising
background image

30

Table 9 – Minimum Allowable Input Rating of

Space--Heating Appliance in Thousands of Btuh per Hour

VENT HEIGHT

FT. (M)

INTERNAL AREA OF CHIMNEY

SQ. IN. (SQ. MM)

12

(7741)

19

(12258)

28

18064)

38

(24516)

Local 99% Winter Design Temperature: 17 to 26 degrees F

6

0

55

99

141

8

52

74

111

154

10

NR

90

125

169

15

NR

NR

167

212

20

NR

NR

212

258

30

NR

NR

NR

362

Local 99% Winter Design Temperature: 5 to 16 degrees F*

6

NR

78

121

166

8

NR

94

135

182

10

NR

111

149

198

15

NR

NR

193

247

20

NR

NR

NR

293

30

NR

NR

NR

377

Local 99% Winter Design Temperature: ---10 to 4 degrees F*

6

NR

NR

145

196

8

NR

NR

159

213

10

NR

NR

175

231

15

NR

NR

NR

283

20

NR

NR

NR

333

30

NR

NR

NR

NR

Local 99% Winter Design Temperature: ---11 degrees F or

lower

Not recommended for any vent configuration.

*The 99.6% heating (db) temperatures found in the 1997 or 2001

ASHRAE Fundamentals Handbook, Climatic Design Information chapter,

Table 1A (United States) and 2A (Canada) or the 2005 ASHRAE Funda-

mentals handbook, Climatic Design Information chapter, and the CD---

ROM included with the 2005 ASHRAE Fundamentals Handbook.

Air for combustion must not be contaminated by halogen

compounds which include chlorides, fluorides, bromides, and
iodides. These compounds are found in many common home

products such as detergent, paint, glue, aerosol spray, bleach,
cleaning solvent, salt, and air freshener, and can cause corrosion

of furnaces and vents. Avoid using such products in the

combustion--air supply. Furnace use during construction of the
building could cause the furnace to be exposed to halogen

compounds, causing premature failure of the furnace or venting
system due to corrosion.
Vent dampers on any appliance connected to the common vent

can cause condensation and corrosion in the venting system. Do
not use vent dampers on appliances common vented with this

furnace.

Additional Venting Requirements
A 4--in. (102 mm) round vent elbow is supplied with the furnace.

A 5--in. (127 mm) or 6-- in. (152 mm) vent connector may be
required for some model furnaces. A field--supplied 4--in. (102

mm) to 5--in. (127 mm) or 4--in. (102 mm) to 6--in. (152 mm)
sheet metal increaser fitting is required when 5--in. (127 mm) or

6--in. (152 mm) vent connector is used. See Fig. 36 -- 48, Venting

Orientation for approved vent configurations.
NOTE: Vent connector length for connector sizing starts at
furnace vent elbow. The 4--in. (102 mm) vent elbow is shipped
for upflow configuration and may be rotated for other positions.
Remove the three screws that secure vent elbow to furnace, rotate
furnace vent elbow to position desired, reinstall screws. The
factory--supplied vent elbow does NOT count as part of the
number of vent connector elbows.
The vent connector can exit the furnace through one of five
locations on the casing.

CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care

and wear appropriate protective clothing, safety glasses and

gloves when handling parts, and servicing furnaces.

CAUTION

!

1. Attach the single wall vent connector to the furnace vent

elbow, and fasten the vent connector to the vent elbow
with at least two field--supplied, corrosion--resistant, sheet

metal screws located 180_ apart.

NOTE: An accessory flue extension is available to extend from
the furnace elbow to outside the furnace casing. See Table 17 for
accessory listing. If flue extension is used, fasten the flue
extension to the vent elbow with at least two field--supplied,
corrosion--resistant, sheet metal screws located 180_ apart. Fasten
the vent connector to the flue extension with at least two
field--supplied, corrosion resistant sheet metal screws located
180_ apart.

2. Vent the furnace with the appropriate connector as shown

in Fig. 36 -- 48.

3. Determine the correct location of the knockout to be re-

moved.

4. Use a hammer and screwdriver to strike a sharp blow

between the tie points and work the slug back and forth
until the slug breaks free.

An accessory Vent Guard Kit is REQUIRED for downflow
applications for use where the vent exits through the lower

portion of the furnace casing. Refer to the Vent Guard Kit
Instructions for complete details. See Table 17 for accessory

listing.

315AA

V