Warning, Caution – Bryant Gas Furance 315AAV User Manual

Page 19

Advertising
background image

19

Return Air Connections

FIRE HAZARD
A failure to follow this warning could cause personal injury,

death and/or property damage.
Never connect return--air ducts to the back of the furnace.

Follow instructions below.

!

WARNING

Downflow Furnaces
The return--air duct must be connected to return--air opening

(bottom inlet) as shown in Fig. 3. DO NOT cut into casing sides
(left or right). Side opening is permitted for only upflow and

certain horizontal furnaces. Bypass humidifier connections
should be made at ductwork or coil casing sides exterior to

furnace. (See Fig. 19.)
Upflow and Horizontal Furnaces
The return--air duct must be connected to bottom, sides (left or

right), or a combination of bottom and side(s) of main furnace
casing as shown in Fig. 3. Bypass humidifier may be attached

into unused return air side of the furnace casing. (See Fig. 18 and
20.) Not all horizontal furnace models are approved for side

return air connections. (See Fig. 20.)
GAS PIPING

FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal

injury, death, and/or property damage.
Never purge a gas line into a combustion chamber. Never

test for gas leaks with an open flame. Use a commercially

available soap solution made specifically for the detection

of leaks to check all connections.

!

WARNING

FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal

injury, death, and/or property damage.
Use proper length of pipe to avoid stress on gas control

manifold and a gas leak.

!

WARNING

FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal

injury, death, and/or property damage.
Gas valve inlet and/or inlet pipe must remain capped until

gas supply line is permanently installed to protect the valve

from moisture and debris. Also, install a sediment trap in the

gas supply piping at the inlet to the gas valve.

!

WARNING

Gas piping must be installed in accordance with national and
local codes. Refer to current edition of NFGC in the U.S.
Installations must be made in accordance with all authorities

having jurisdiction. If possible, the gas supply line should be a
separate line running directly from meter to furnace.

NOTE: In the state of Massachusetts:

1. Gas supply connections MUST be performed by a li-

censed plumber or gas fitter.

2. When flexible connectors are used, the maximum length

shall not exceed 36 in. (915 mm).

3. When lever handle type manual equipment shutoff valves

are used, they shall be T--handle valves.

4. The use of copper tubing for gas piping is NOT approved

by the state of Massachusetts.

Refer to Table 6 for recommended gas pipe sizing. Risers must be

used to connect to furnace and to meter. Support all gas piping

with appropriate straps, hangers, etc. Use a minimum of 1 hanger
every 6 ft. (1.8 M). Joint compound (pipe dope) should be

applied sparingly and only to male threads of joints. Pipe dope
must be resistant to the action of propane gas.

Table 6 – Maximum Capacity of Pipe

NOMINAL

IRON PIPE

SIZE

IN. (MM)

INTERNAL

DIA.

IN. (MM)

LENGTH OF PIPE --- FT (M)

10

(3.0)

20

(6.0)

30

(9.1)

40

(12.1)

50

(15.2)

1/2 (12.7)

0.622(158)

175

120

97

82

73

3/4 (19.0)

0.824 (20.9)

360

250

200

170

151

1 ( 25.4)

1.049 (26.6)

680

465

375

320

285

1-1/4

(31.8)

1.380 (35.0)

1400

950

770

660

580

1-1/2

(38.1)

1.610 (40.9)

2100

1460

1180

990

900

* Cubic ft of gas per hr for gas pressures of 0.5 psig (14--- In. W.C.) or less and

a pressure drop of 0.5--- In. W.C. (based on a 0.60 specific gravity gas). Ref:

Table 6 and 9.2 NFGC.

FIRE OR EXPLOSION HAZARD
A failure to follow this warning could result in personal

injury, death, and/or property damage.
If local codes allow the use of a flexible gas appliance

connector, always use a new listed connector. Do not use a

connector which has previously served another gas

appliance. Black iron pipe shall be installed at the furnace

gas control valve and extend a minimum of 2--in. (51 mm)

outside the furnace.

!

WARNING

FURNACE DAMAGE HAZARD
Failure to follow this caution may result in furnace damage.
Connect gas pipe to furnace using a backup wrench to

avoid damaging gas controls and burner misalignment.

CAUTION

!

An accessible manual equipment shutoff valve MUST be

installed external to furnace casing and within 6 ft. (1.8 M) of
furnace. A 1/8--in. (3 mm) NPT plugged tapping, accessible for

test gauge connection, MUST be installed immediately upstream

of gas supply connection to furnace and downstream of manual
equipment shutoff valve.
NOTE:

The furnace gas control valve inlet pressure tap

connection is suitable to use as test gauge connection providing
test pressure DOES NOT exceed maximum 0.5 psig (14--In.
W.C.) stated on gas control valve. (See Fig. 50.)
Some installations require gas entry on right side of furnace (as

viewed in upflow). (See Fig. 21.)
Install a sediment trap in riser leading to furnace as shown in Fig.

22. Connect a capped nipple into lower end of tee. Capped nipple

315AA

V

Advertising