Warning, Caution, Start--up, adjustment, and safety check – Bryant Gas Furance 315AAV User Manual

Page 34

Advertising
background image

34

Caution!! For the following applications, use the minimum vertical heights as specified below.

For all other applications, follow exclusively the National Fuel Gas Code.

FURNACE

ORIENTATION

VENT ORIENTATION

FURNACE INPUT

(BTUH/HR)

MIN. VENT

DIAMETER

IN. (mm)*

MIN. VERTICAL VENT

HEIGHT

FT. (M)**

Downflow

Vent elbow left, then up

Fig.

36

154,000 132,000 110,000

5 (127)

12 (3.6)

Horizontal Left

Vent elbow right, then up

Fig.

39

154,000 132,000

5 (127)

7 (2.1)

Horizontal Left

Vent Elbow up

Fig.

40

154,000 132,000

5 (127)

7 (2.1)

Horizontal Left

Vent elbow right

Fig.

41

154,000

5 (127)

7 (2.1)

Downflow

Vent elbow up then left

Fig. 34

110,000

5 (127)

10 (3.0)

Downflow

Vent elbow up, then right

Fig.

37

110,000

5 (127)

10 (3.0)

NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC.
*4---in. (102 mm) inside casing or vent guard
**Including 4 in. (102 mm) vent section(s)

The horizontal portion of the venting system shall slope upwards
not less than 1/4--in. per linear ft. (21 mm/m) from the furnace to

the vent and shall be rigidly supported every 5 ft. (1.5 M) or less
with metal hangers or straps to ensure there is no movement after

installation.
Sidewall Venting
This furnace is not approved for direct sidewall horizontal

venting.
Per section 12.4.3 of the NFPA 54/ANSI Z223.1--2009, any

listed mechanical venter may be used, when approved by the
authority having jurisdiction.
Select the listed mechanical venter to match the Btuh input of the

furnace being vented. Follow all manufacturer’s installation
requirements for venting and termination included with the listed

mechanical venter.

START--UP, ADJUSTMENT, AND SAFETY

CHECK

General

FIRE HAZARD
Failure to follow this warning could result in personal injury,

death or property damage.
This furnace is equipped with manual reset limit switches in

the gas control area. The switches open and shut off power to

the gas valve, if a flame rollout or overheating condition

occurs in the gas control area. DO NOT bypass the switches.

Correct problem before resetting the switches.

!

WARNING

1. Maintain 115--v wiring and ground. Improper polarity will

result in rapid flashing LED and no furnace operation.

2. Make thermostat wire connections at the 24--v terminal

block on the furnace control. Failure to make proper con-

nections will result in improper operation. (See Fig. 25 --
34.)

3. Gas supply pressure to the furnace must be greater than

4.5--In. W.C. (0.16 psig ) but not exceed 14--In. W.C. (0.5

psig).

4. Check all manual--reset switches for continuity.
5. Replace blower compartment door. Door must be in place

to operate furnace.

6. Setup switch descriptions The variable speed furnace con-

trol has DIP switches to select thermostat staging, blower
off delay timings, air flow selection and other operational
or service related functions. (See Fig. 26, 53 and Table

10.)

CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care

and wear appropriate protective clothing, safety glasses and

gloves when handling parts, and servicing furnaces.

CAUTION

!

REGULATOR COVER SCREW

PLASTIC ADJUST SCREW

LOW STAGE
GAS PRESSURE
REGULATOR ADJUSTMENT

MANIFOLD
PRESSURE TAP

INLET
PRESSURE TAP

ON/OFF SWITCH

REGULATOR SPRING

HIGH STAGE GAS
PRESSURE REGULATOR
ADJUSTMENT

1/2˝ NPT OUTLET

1/2˝ NPT INLET

A04167

Fig. 49 -- Redundant Automatic Gas Control Valve

315AA

V