Upflow downflow horizontal – Bryant Gas Furance 315AAV User Manual

Page 14

Advertising
background image

14

Supply Air Connections
For a furnace not equipped with a cooling coil, the outlet duct

shall be provided with a removable access panel. This opening
shall be accessible when the furnace is installed and shall be of

such a size that the heat exchanger can be viewed for possible
openings using light assistance or a probe can be inserted for

sampling the air stream. The cover attachment shall prevent leaks.
Upflow and Horizontal Furnaces
Connect supply--air duct to flanges on furnace supply--air outlet.

Bend flange upward to 90_ with wide duct pliers. (See Fig. 14.)
The supply--air duct must be connected to ONLY the furnace

supply--outlet--air duct flanges or air conditioning coil casing
(when used). DO NOT cut main furnace casing side to attach

supply air duct, humidifier, or other accessories. All accessories
MUST be connected to duct external to furnace main casing.

NOTE: For horizontal applications, the top most flange may be
bent past 90_ to allow the evaporator coil to hang on the flange
temporarily while the remaining attachment and sealing of the
coil are performed.
Downflow Furnaces
Connect supply--air duct to supply--air outlet on furnace. Bend

flange inward past 90_ with wide duct pliers (See Fig. 14.) The

supply--air duct must be connected to ONLY the furnace supply
outlet or air conditioning coil casing (when used). When installed

on combustible material, supply--air duct must be connected to
ONLY the factory--approved accessory subbase, or a

factory--approved air conditioning coil casing. DO NOT cut main

furnace casing to attach supply side air duct, humidifier, or other
accessories. All accessories MUST be connected to duct external

to furnace casing.

UPFLOW

DOWNFLOW

HORIZONTAL

YES

NO

NO

YES

YES

YES

NO

120

°

MIN

YES

120

°

MIN

YES

120

°

MIN

90

°

90

°

A02020

Fig. 14 -- Duct Flanges

315AA

V

Advertising