Caution, Warning, Air for combustion and ventilation – Bryant Gas Furance 315AAV User Manual

Page 8

Advertising
background image

8

Table 2 – Minimum Free Area Required for Each Combustion Air opening of Duct to Outdoors

FURNACE

INPUT

(BTUH)

TWO HORIZONTAL DUCTS

SINGLE DUCT OR OPENING

TWO OPENINGS OR VERTICAL DUCTS

(1 SQ. IN./2,000 BTUH) (1,100 SQ. MM/KW)

(1 SQ. IN./3,000 BTUH) (734 SQ. MM/KW)

(1 SQ. IN./4,000 BTUH) (550 SQ. MM/KW)

Free Area of Opening

and Duct

Sq. In. (Sq. mm)

Round Duct

Dia.

In. (mm)

Free Area of Opening

and Duct

Sq. In. (Sq. mm)

Round Duct

Dia.

In. (mm)

Free Area of Opening

and Duct

Sq. In. (Sq. mm)

Round Duct

Dia.

In. (mm)

44,000

22 (14194)

6 (152)

14.7 (9484)

5 (127)

11 (7096)

4 (102)

66,000

33 (21290)

7 (178)

22 (14193)

6 (152)

16.5 (10645)

5 (127)

88,000

44 (28387)

8 (203)

29.3 (18903)

7 (178)

22 (14193)

6 (152)

110,000

55 (35484)

9 (229)

36.7 (23677)

7 (178)

27.5 (17742)

6 (152)

132,000

66 (42580)

10 (254)

44 (28387)

8 (203)

33 (21290)

7 (178)

154,000

77 (49677)

10 (254)

51.3 (33096)

9 (229)

38.5 (24839)

8 (203)

EXAMPLES: Determining Free Area

FURNACE

WATER HEATER

TOTAL INPUT

110,000

+

30,000

=

(140,000 divided by 4,000)

=

35.0 Sq. In. for each two Vertical Ducts or Openings

66,000

+

40,000

=

(106,000 divided by 3,000)

=

35.3 Sq. In. for a Single Duct or Opening

88,000

+

30,000

=

(118,000 divided by 2,000)

=

59.0 Sq. In. for each of two Horizontal Ducts

Table 3 – Minimum Space Volumes for 100% Combustion, Ventilation, and Dilution from Indoors

OTHER THAN FAN-ASSISTED TOTAL

(1,000’S BTUH GAS INPUT RATE)

FAN-ASSISTED TOTAL

(1,000’S BTUH GAS INPUT RATE)

ACH

30

40

50

44

66

88

110

132

154

Space Volume Ft

3

(M

3

)

0.60

1,050

(29.7)

1,400

(39.6)

1,750

(49.5)

1,100

(31.1)

1,650

(46.7)

2,200

(62.2)

2,750

(77.8)

3,300

(93.4)

3,850

(109.0)

0.50

1,260

(35.6)

1,680

(47.5)

2,100

(59.4)

1,320

(37.3)

1,980

(56.0)

2,640

(74.7)

3,300

(93.4)

3,960

(112.1)

4,620

(130.8)

0.40

1,575

(44.5)

2,100

(59.4)

2,625

(74.3)

1,650

(46.7)

2,475

(70.0)

3,300

(93.4)

4,125

(116.8)

4,950

(140.1)

5,775

(163.5)

0.30

2,100

(59.4)

2,800

(79.2)

3,500

(99.1)

2,200

(62.2)

3,300

(93.4)

4,400

(124.5)

5,500

(155.7)

6,600

(186.8)

7,700

(218.0)

0.20

3,150

(89.1)

4,200

(118.9)

5,250 (148.6)

3,300

(93.4)

4,950

(140.1)

6,600

(186.8)

8,250

(233.6)

9,900

(280.3)

11,550

(327.0)

0.10

6,300

(178.3)

8,400

(237.8)

10,500

(297.3)

6,600

(186.8)

9,900

(280.3)

13,200

(373.7)

16,500

(467.2)

19,800

(560.6)

23,100

(654.1)

0.00

NP

NP

NP

NP

NP

NP

NP

NP

NP

NP = Not Permitted

AIR FOR COMBUSTION AND

VENTILATION

Provisions for adequate combustion, ventilation, and dilution air

must be provided in accordance with:

S

U.S. Installations: Section 9.3 of the NFPA 54/ANSI
Z223.1--2009 , Air for Combustion and Ventilation and
applicable provisions of the local building codes.

FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace damage.
Air for combustion must not be contaminated by halogen

compounds, which include fluoride, chloride, bromide, and

iodide. These elements can corrode heat exchangers and

shorten furnace life. Air contaminants are found in aerosol

sprays, detergents, bleaches, cleaning solvents, salts, air

fresheners, and other household products.

CAUTION

!

CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal

injury or death.
The operation of exhaust fans, kitchen ventilation fans,

clothes dryers, attic exhaust fans or fireplaces could create a

NEGATIVE PRESSURE CONDITION at the furnace.

Make--up air MUST be provided for the ventilation devices,

in addition to that required by the furnace. Refer to the

Carbon Monoxide Poisoning Hazard warning in the venting

section of these instructions to determine if an adequate

amount of make--up air is available.

!

WARNING

The requirements for combustion and ventilation air depend upon

whether or not the furnace is located in a space having a volume
of at least 50 cubic feet per 1,000 Btuh input rating for all gas

appliances installed in the space.

S

Spaces having less than 50 cubic feet per 1,000 Btuh
require the OUTDOOR COMBUSTION AIR

METHOD.

315AA

V

Advertising