Bryant Gas Furance 315AAV User Manual

Page 22

Advertising
background image

22

A10141

Fig. 24 -- Field--Supplied Electrical Box on Furnace Casing

Power Cord Installation in Furnace J--Box
NOTE
: Power cords must be able to handle the electrical
requirements listed in Table 6. Refer to power cord
manufacturer’s listings.

1. Remove cover from J--Box.
2. Route listed power cord through 7/8--in. (22 mm) diameter

hole in J--Box.

3. Secure power cord to J--Box bracket with a strain relief

bushing or a connector approved for the type of cord used.

4. Secure field ground wire to green ground screw on J--Box

bracket.

5. Connect line voltage leads as shown in Fig. 25.
6. Reinstall cover to J--Box. Do not pinch wires between

cover and bracket.

BX Cable Installation in Furnace J--Box

1. Remove cover from J--Box.

2. Route BX cable into 7/8--in. (22 mm) diameter hole in

J--Box.

3. Secure BX cable to J--Box bracket with connectors ap-

proved for the type of cable used.

4. Secure field ground wire to green ground screw on J--Box

bracket.

5. Connect line voltage leads as shown in Fig. 25.
6. Reinstall cover to J--Box. Do not pinch wires between

cover and bracket.

24--V Wiring
Make field 24--v connections at the 24--v terminal strip. (See Fig.
25 -- 34.) Connect terminal Y/Y2 as shown in Fig. 27--34 for

proper cooling operation. Use only AWG No. 18, color--coded,

copper thermostat wire.
The 24--v circuit contains an automotive--type, 3--amp. fuse

located on the control. Any direct shorts during installation,
service, or maintenance could cause this fuse to blow. If fuse

replacement is required, use ONLY a 3--amp. fuse of identical
size.
ACCESSORIES

1. Electronic Air Cleaner (EAC)

Connect an accessory Electronic Air Cleaner (if used) us-
ing 1/4--in female quick connect terminals to the two male

1/4--in quick--connect terminals on the control board
marked EAC--1 and EAC--2. The terminals are rated for
115VAC, 1.0 amps maximum and are energized during

blower motor operation. (See Fig. 26.)

2. Humidifier (HUM)

Connect an accessory 24 VAC, 0.5 amp. maximum hu-
midifier (if used) to the 1/4--in male quick--connect HUM

terminal and COM--24V screw terminal on the control
board thermostat strip. The HUM terminal is energized
when blower is energized in heating. (See Fig. 26.)

NOTE: DO NOT connect furnace control HUM terminal to
HUM (humidifier) terminal on Thermidistat, Zone Controller or
similar device. See ThermidistatE, Zone Controller, thermostat,
or controller manufacturer’s instructions for proper connection.
VENTING
The furnace shall be connected to a listed factory built chimney

or vent, or a clay--tile lined masonry or concrete chimney. Venting

into an unlined masonry chimney or concrete chimney is
prohibited.
When an existing Category I furnace is removed or replaced, the
original venting system, may no longer be sized to properly vent

the attached appliances. An improperly sized Category I venting

system could cause the formation of condensate in the furnace
and vent, leakage of condensate and combustion products, and

spillage of combustion products into the living space.

315AA

V

Advertising