Lift cabin audio unit – compact 2.3, 42 alarm button connection with n/c contact, Voltage activation – 2N Lift emergency phone 2N LiftNet - Manual, 1446 v1.8.3 User Manual

Page 42

Advertising
background image

Lift Cabin Audio Unit

– Compact

2.3

42

ALARM Button Connection with N/C Contact

Note

The ALARM button mounted on the cover is still functional when an
external button is connected.

Voltage Activation

Caution

5 - 24 dc voltage of any polarity can be used. Make sure that the power
supply is backed up properly.

Where activation from multiple places is necessary, voltage control can be
combined with buttons.

A buzzer or horn can be connected in parallel, see the figure to the right.

Figure 2.15 ALARM
Button Connection with
N/C Contact

Figure 2.16 Voltage Activation

Advertising