Emergency Alarm
Push the Set emergency alarm button and confirm the button settings in the next
window to enable emergency alarm. The emergency alarm will start alerting in 20
seconds.
is responsible for emergency alerting of all stations
2N NetStar Assistant
®
in the group for which the alarm was enabled. The 20s timeout enables the emergency
alarm to be cancelled in the case of error as it cannot be cancelled once alerting starts.
The moment all stations are answered and the voice message is heard, 2N NetStar
®
considers the emergency alarm process terminated. If a station fails to
Assistant
answer or rejects the emergency alarm call, it will be redialled after a preset time
interval, which is identical with the alarm clock interval, i.e. three times within three
minutes. If the calls are still unsuccessful, the station will not be alerted any more.