Installation

jina

85

e 4

.fm

Tech

ni

ca

l Ha

nd

bo

ok

(1

11

2)

4.6.2

Electrical connection of the PLC inputs

The default setting is as follows:

Signal level:

24 V (low-resistance) means High,

0 V (high-resistance) means Low,

Change from LOW to HIGH:

The programmed command for the input is enabled (edge controlled).

Pin

Command

Explanation

1

Start

2

Stop

3

Cal

4

Proof

5

Clear:

6

Standby

7

Common

Common negative pole for all PLC inputs.
Connect to the negative pole of the power supply.

Caution

Max. permissible input voltage of the digital inputs: 28 V.

Fig. 5-2 Electrical connection of the PLC inputs