5 analog output, 1 function, 2 signal type – JUMO 14597 safetyM STB/STW Ex - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual
Page 104: 3 scaling start, 4 scaling end, Analog output, Function, Signal type, Scaling start, Scaling end

8 Configuration level
98
8.5
Analog output
Parameter
Comment
Value range
(factory setting in
bold)
8.5.1 Function
Here, the measured value that is to be shown at the
analog output is set.
Main measured value
Measured value1
Measured value2
Difference
Main measured value:
With the max. alarm switching behavior, the greater of
the two measured values is shown; with the min. alarm,
the lower of the two measured values is shown.
Measured value1:
Measured value of analog input 1 (E1) is shown
Measured value2:
Measured value of analog input 2 (E2) is shown
Difference:
E1-E2 is shown
The signal that should be output by the analog output
can be set with scaling start and end.
8.5.2 Signal type
4 to 20 mA
4 to 20 mA
0 to 20 mA
2 to 10 V
0 to 10 V
0 to 20 mA
2 to 10 V
0 to 10 V
8.5.3 Scaling start
v
Figure in Chapter 8.5.6
-9999 to
-200 to +9999
8.5.4 Scaling end
v
Figure in Chapter 8.5.6
-9999 to
800 to +9999