5 startup of the device, 1 display and control elements, 2 setting the display after device is switched on – JUMO 14597 safetyM STB/STW Ex - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual
Page 29: Startup of the device, Display and control elements, Setting the display after device is switched on, 5startup of the device

5 Startup of the device
23
5
Startup of the device
5.1
Display and control elements
h
When the voltage supply is set up, a testing routine starts during which all LEDs blink and the backlit display shows white
pixels for 2 s and black pixels for 2 s.
After the testing routine is complete the device shows a main measured value (factory set).
v
If an alarm or error message appears, refer to Chapter 11 "Alarm messages".
5.2
Setting the display after device is switched on
v
Chapter 8.6.4 "Normal display"
The main measured value appears on the screen in German (this is factory set). The example shows a screen layout in which
the maximum value of a safety temperature limiter of 70 °C with a pre-alarm of 60 °C is monitored.
H
If the main measured value for "Power ON" lies within the hysteresis then the pre-alarm and alarm relay outputs are
set to inactive.
(1) Switching behavior
(2) Device function
(3) Binary input
(7) Main measured value
(6) Pre-alarm
(4) Temperature unit
(5) Limit value