9 technical data, 1 analog inputs, Technical data – JUMO 14597 safetyM STB/STW Ex - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual
Page 110: Analog inputs, 9technical data

9 Technical data
104
9
Technical data
9.1
Analog inputs
RTD temperature probes
Thermocouples
Description
Measuring range
Accuracy
2/3-wire circuit
1
Ambient temperature
influence
Pt100 DIN EN 60751
-200 to +850 °C
0.5 % / 0.1 %
50 ppm/K
Pt1000 DIN EN 60751
-200 to +850 °C
0.5 % / 0.1 %
50 ppm/K
Connection type
2-wire, 3-wire circuit
Maximum lead wire resistance 30
Ω
Sampling rate
210 ms
Fault tolerance time
≤
5 s time taken into account for all diagnostic tests
Input filter
Digital filter, 2nd order; filter constant can be set from 0 to 100 s
Special features
Individual probe Pt100 2-wire,
display can also be programmed in °F
Description
Measuring range
Accuracy
1
Ambient temperature influ-
ence
Fe-CuNi "L" DIN 43710
-200 to +900 °C
0.4 %
100 ppm/K
Fe-CuNi "J" DIN EN 60584
-200 to +1200 °C
0.4 %
100 ppm/K
Cu-CuNi "U" DIN 43710
-200 to +600 °C
0.4 %
100 ppm/K
Cu-CuNi "T" DIN EN 60584
-200 to +400 °C
0.4 %
100 ppm/K