10 Setup program
121
3
h
In the Analog input menu, set
Single 4 to 20 mA. Further
input fields for scaling appear.
h
For both channels, enter
Start: 0 and End: 500 and con-
firm with OK.
4
h
In the Limiter/Monitor menu, set
STB or Initial STB com-
missioning. Set Switching behavior: to Min. alarm and
confirm with OK.
h
Enter the required
limit value (in Pa) and hysteresis.
Step
Action
Description