2 analog inputs, 1 connection, Analog inputs – JUMO 14597 safetyM STB/STW Ex - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual
Page 93: Connection, 8 configuration level

8 Configuration level
87
8.2
Analog inputs
k
Factory setting
8.2.1 Connection
Comment
Two sensors
This setting is provided for dual probes or for two different probes.
Each of the two analog inputs is monitored separately for a probe break or
probe short-circuit.
Single Pt100 in 2-wire circuit
V
Caution:
When only one probe (SIL2) is connected, the temperature limiter device is
reduced from
SIL3 to SIL2.
However, the internal 2-channel structure (1oo2D) in the device still remains.
Both channels measure the same sensor due to the simplified external wiring.
Single 4 to 20 mA
V
Caution:
When only one probe (SIL2) is connected, the temperature limiter device is
reduced from
SIL3 to SIL2.
However, the internal 2-channel structure (1oo2D) in the device still remains.
Both channels measure the same current signal due to the simplified external
wiring.