4 Electrical connection

19

2013-04-01

Legend Comment

Screw terminals

Screw terminals

1, 2

Analog input 1 (E1)

Analog input 2 (E2)

Thermocouple /

Double thermocouple

RTD temperature probe Pt100/Pt1000 in

2-wire circuit

RTD temperature probe Pt100/Pt1000 in

3-wire circuit

V

RTD temperature probe Pt100 in
2-wire circuit, single sensor for both analog inputs

Caution:
When only one probe (SIL2) is connected, the temperature limiter device is reduced from

SIL3 to SIL2! However,

the internal 2-channel structure (1oo2D) in the device still remains.
Both channels measure the same sensor due to the simplified external wiring.

+

2

3

+

7

8

J

1

3

J

6

8

A

Enter the lead wire resistance for RTD temperature probes in 2-wire circuit when using greater line
lengths.

v

Setup program: edit => analog inputs