2 removing the cover cap, Removing the cover cap, 4 electrical connection – JUMO 14597 safetyM STB/STW Ex - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual
Page 23

4 Electrical connection
17
4.2
Removing the cover cap
V
The electrical connection and the configuration settings up to the startup must only be carried out by qualified per-
sonnel.
A
The approval according to DIN EN 14597 is only valid when the correct probe with DIN approval is set in the config-
uration level and if the probe is connected.
The limit value to be monitored must lie in the accepted temperature range of the DIN probe!
v
Chapter 9.13 "Probes for the operating medium air"
v
Chapter 9.15 "Probes for air, water, and oil"
The monitoring function is deactivated while data is transmitted over the setup program.
v
Chapter 13 "What to do, if ..."
1
h
Stick the screwdriver in the right open-
ing of the cover cap and pry up to the
left.
2
h
Hold the cover cap and pry up the sec-
ond catch in the left opening to the right.