12 Error messages
124
12 Error messages
These error messages are displayed one below the other.
Error display (Err)
Origin
Cause/remedy
Internal
The set limit value for relay switching cycles has been reached
h
Increase the limit value for the relay switching cycles
v
Chapter 8.7.1 "Limit switching cycle"
Instead of the bell, a cross appears and the error message can be acknowl-
edged.
Terminal temp.
Internal
The internal Pt100 is defective
1
, or the terminal temperature is outside the ad-
missible range (-10 to 80 °C).
This error cannot be acknowledged until it is within the admissible range
again.
Reference volt.
1
Internal
The reference voltage is outside the valid range.
Acknowledgement is not possible until it is within the valid range again.
Calibration const.
1
Internal
A calibration constant is outside the valid range.
Acknowledgement is not possible until it is within the valid range again.
Configuration
Internal
Configuration data outside the value range.
Acknowledgement is not possible until it is within the valid range again.
Measured value
Internal
The measured value 1 or 2 is outside the valid range.
Acknowledgement is not possible until it is within the valid range again.