Drive setup & operation, 1 control parameter, 2 serial address – Lenze smd Series Drives User Manual

Page 12: 3 serial communications parameter

Advertising
background image

RG-SDMOD 8

Drive Setup & Operation

4

smd

Drive Setup & Operation

4.1 Control Parameter

In order to communicate using Modbus protocol, the

smd Control Source Setpoint (parameter #C01) must

be set to one of the selections listed in Table 4.

Table 4: Control Source Setpoint C01 (Register 51)

Setting

Source

Description

Program

(Monitoring)

Control

(Start/Stop,
Direction)

Speed

(Source)

8

Modbus

Terminal

Analog Input Drive is controlled via terminal programming and is monitored via Modbus

interface or keypad. The default speed source is the analog input.

9

Modbus

Terminal

c40

Drive is controlled via terminal programming and is monitored via Modbus
interface or keypad. The default speed source is c40.

10

Modbus

Modbus

Analog Input Drive is controlled via serial interface and is monitored via Modbus

interface or keypad. The default speed source is the analog input.

11

Modbus

Modbus

c40

Drive is controlled via serial interface and is monitored via Modbus
interface or keypad. The default speed source is c40

4.2 Serial Address

The

smd drive has a serial address parameter that must be programmed prior to attempting to operate the

serial interface. Set Parameter C09 (Network Address) to a valid address (1-247).

Tip
Most Modbus devices ship with a default address of 1. As such, it is recommended to

not

use address 1 in order to avoid duplicate address conflicts when replacing devices.

4.3 Serial Communications Parameter

Lenze-AC Tech drives have a Serial Communications Parameter that governs the operation of the serial
link. On

smd drives this is c25, Serial Baud Rate {Register #95 (PC400) or #103 (PC507)}. Parameter C01

Control Source Setpoint must first be set to a value of 8-11. Table 5a lists the selections for

smd Parameter

c25, Serial Baud Rate. Table 5b lists the selections for the controller's reaction to serial timeout (n22).

Tables 5a & 5b: Serial Communications

Table 5a: Serial Baud Rate c25

Table 5b: Serial Timeout Action n22

Setting

Description

Setting

Description

0

9600, 8, N, 2

0

Not active

1

9600, 8, N, 1

1

Inhibit

2

9600, 8, E, 1

2

Quick Stop

3

9600, 8, O, 1

3

Trip Fault FC3

The Serial Communications Parameter (c25) must be appropriately programmed prior to attempting to
communicate with the drive. The timeout period is programmed in Parameter n23, Serial Fault Time.

Advertising