3 RG-SDMOD

Introduction

2 Introduction

This document defines the specifics required for Modbus serial communication with a Lenze-AC Tech
standard

smd Series drive for control, status monitoring, and programming parameters. A familiarity

with normal drive capabilities and operations is assumed. If this is not the case, refer to the

smd Series

Operating Instructions (SL03) for more information.

2.1 RS485 Details

Only standard

smd models with an “L” as the eighth digit in the model number (ex. ESMD371L4TXA) are

equipped with Modbus RS-485 capabilities. When using this feature the drive can communicate with a
personal computer (PC), programmable logic controller (PLC), or other external device that utilizes Modbus
RS-485 serial communication for control or monitoring. Refer to the

smd Operating Instructions (SL03) for

connection details. Figure 1 illustrates the

smd control strip. Terminals 7 (COM), 71 (TXB) and 72 (TXA) are

used for RS485 communication.

U V W

L1 L2

8 9 20 28 E1 E2 E3

K14 K12

+10

V

+12

V

COM

AIN

7

71 72

L3

20 A1 62

TXA

TXB

COM

Figure 1:

smd Control Strip

2.2 Electrical Installation

2.2.1 Cable Type

For RS485 Modbus networks, use a quality shielded twisted pair cable. The use of low quality cable will
result in excess signal attenuation and data loss.

2.2.2 Connections and Shielding

To ensure good system noise immunity all networks cables should be correctly grounded:
• Minimum grounding recommendation: ground the network cable shield once in every cubical.
• Ideal grounding recommendation: ground the network cable on or as near to each drive as possible.
• For wiring of cable to the

smd control terminal, the unscreened cable cores should be kept as short as

possible; recommended maximum of 20mm. Ground the shield at the drive end only.

• In addition, grounding terminal 7 on the

smd is recommended when using serial communications.