25 RG-SDMOD

Drive Control & Communication

7

Quick Start Instructions

Follow these Quick Start instructions to use Modbus Communications for basic network control of an
smd drive. These instructions are for basic start, stop, direction and speed control of the smd drive. To
download the

smd manual visit the Lenze-AC Tech Technical Library at http://www.lenze-actech.com.

7.1 Initial Settings

These instructions are for basic start, stop direction and speed control of the smd drive using Modbus
communication.

1. Set Drive Parameter C01 to 11.

2. Set Drive Parameter C09 to the desired network address that the Modbus master will poll. Valid Modbus

addresses are 1-247.

TIP - Avoid using address 1. Most Modbus devices ship with a default address of 1. As duplicate
addressing on a Modbus network is not allowed, this can lead to conflicts when replacing and
commissioning nodes. To avoid this it is recommended that you do not set the slave address to 1.

3. The Modbus master needs to be set to use 9600 baud. No other baud rates are supported by the SMD

drive.

4. The SMD series drive has the provision for a watchdog timer to monitor network communications to

the drive. The drive’s timeout behavior is set using Parameter n22 and the timeout period is set using
Parameter n23 as shown in Table 19.

Table 19: Watchdog Timer

Code

Possible Settings

Important

No.

Name

Lenze Selection

n22

Serial Timeout Action

0

0 Not Active
1 Controller Inhibit
2 Quick Stop
3 Trip Fault "FC3"

Selects controller reaction to
serial timeout

n23

Serial Fault Time

50

50 - 65535 ms

Sets the serial timeout length

Set n22 and n23 as appropriate for the application:

5. The drive needs to have its network data formatting set the same as the Modbus master.

a. If the Modbus master is set to use 8 data bits, no parity and two stop bits, set c25 to 0.

b. If the Modbus master is set to use 8 data bits, no parity and one stop bit, set c25 to 1.

c. If the Modbus master is set to use 8 data bits, even parity and one stop bit, set c25 to 2.

d. If the Modbus master is set to use 8 data bits, odd parity and one stop bit, set c25 to 3.