Drive control & communication, Programming parameters – Lenze smd Series Drives User Manual

Page 23

Advertising
background image

19 RG-SDMOD

Drive Control & Communication

6

smd

Programming Parameters

6.1 Format

NOTE - Attention
Parameter list presented in Section 6.2 is valid only for

smd parameter version 400 and

507. For revisions, refer to appropriate

smd Manual.

Abbreviations:

SA

(1byte) Drive Address (1-247)

RA

(1byte) Register Address

CRCH Cyclic Redundancy Check High byte
CRCL Cyclic Redundancy Check Low byte

READING:

Message structure for reading 1 word: (most of parameters)

Request: SA 03 00 RA 00 01 CRCH CRCL
Response:

SA 03 02 DH DL CRCH CRCL

Message structure for reading 4 word: (Parameter C99 Software Version)

Request: SA 03 00 RA 00 04 CRCH

CRCL

Response: SA 03 08 D1H D1L D2H D2L D3H D3L D4H D4L CRCH CRCL

WRITING:

Message structure for writing 1 word: (all parameters)

Request: SA 06 00 RA DH DL CRCH CRCL
Response:

SA 06 00 RA DH DL CRCH CRCL

LEGEND for Parameter List
1st Column:

Parameter No.

1

= Drive's programming code number

4th Column:

Range of Adjustment

2

= Selections in bold are for

smd models with PV507 only.