Drive control & communication – Lenze smd Series Drives User Manual

Page 26

Advertising
background image

RG-SDMOD 22

Drive Control & Communication

Parameter No.

1

smd Register #

(hexadecimal

representation)

Parameter Name

Range of Adjustment

2,

Modbus value (decimal value)

Factory

Default

PV400

PV507

C38

74 (4AH)

75 (4BH)

Fixed Setpoint 2 (JOG2)

0 - 9990 (0.0 - 999)

30.0 Hz

C39

75 (4BH)

76 (4CH)

Fixed Setpoint 3 (JOG3)

0 - 9990 (0.0 - 999)

40.0 Hz

C46

78 (4EH)

79 (4FH)

Frequency Setpoint

0 - 2400 (0.0 - 240 Hz)

Read Only

C50

79 (4FH)

80 (50H)

Output Frequency

0 - 2400 (0.0 - 240 Hz)

Read Only

C52

80 (50H)

82 (52H)

Motor Voltage

0 - 255%

Read Only

C53

81 (51H)

83 (53H)

DC Bus Voltage

0 - 255%

Read Only

C54

82 (52H)

84 (54H)

Motor Current

0 - 255%

Read Only

C56

83 (53H)

85 (55H)

Drive Load

0 - 255%

Read Only

C59

86 (56H)

PI Actual Feedback

c86 - c87

Read Only

C70

89 (59H)

PI Proportional Gain

0 - 999 (0 - 99.9%)

5.0%

C71

90 (5AH)

PI Integral Gain

0 - 999 (0 - 99.9 sec)

0.0 sec

C90

86 (56H)

92 (5CH)

Input Voltage Selection

0 Auto
1 Low
2 High

0

C94

88 (58H)

94 (5EH)

User Password

0 - 999

0

C99

89 (59H)

95 (5FH)

Software Version

Read 4 words (format 'SMD 1.51')

Read Only

c01

96 (60H)

Accel Rate 2

0 - 9990 (0.0 - 999 sec)

5.0 sec

c03

97 (61H)

Decel Rate 2

0 - 9990 (0.0 - 999 sec)

5.0 sec

c06

90 (5AH)

98 (62H)

Holding Time - Auto
DC Injection Brake

0 - 9990 (0.0 - 999 sec)

0.0 sec

c08

91 (5BH)

99 (63H)

Analog Output Scaling

10 - 9990 (1.0 - 999)

100.0

c11

92 (5CH)

100 (64H) Configuration

Analog Output (62)

0 None
1 Output frequency 0 - 10V
2 Output frequency 2 - 10V
3 Load 0 - 10V
4 Load 2- 10V
5 Dynamic Braking

0

c17

93 (5DH)

101 (65H) Configuration

Digital Output (A1)

0 Ready
1 Fault
2 Motor is running
3 Motor is running - CW rotation
4 Motor is running - CCW rotation
5 Output frquency = 0Hz
6 Frequency setpoint reached
7 Threshold (C17) exceeded
8 Current limit reached
9 Feedback within min/max alarm range
10 Feedback outside min/max alarm range

0

c20

94 (5EH)

102 (66H) I

2

T Switch-Off

30 - 100%

100%

1 = The drive's programming code number; 2 = Selections in

bold are for

smd models with PV507 only.