Technical data

General Data

EDK82ZAFPC-201 DE/EN/FR 6.0

52

H1_Daten-IP20

4

Technical data

General Data

Area

Values

Order designation

E82ZAFPC201

PUO ID number

0x081B

hex

Communication profile
(DIN 19245 Part 1 and Part 3)

PROFIBUS-DP-V0
PROFIBUS-DP-V1

Communication medium

RS485

Drive profile

DRIVECOM profile ”Drive technology 20” (can be switched off)
PROFIdrive (can be switched off, state machine and PROFIdrive
parameter data channel)

Network topology

Without repeaters: line
With repeaters: line or tree

PROFIBUS bus device

Slave

Baud rate [kbps]

9.6 ... 12000 (automatic detection)

Process data words

1 ... 10 words
(16 bits/word)

DP user data length

1 ... 10 process data words +
4 parameter data words

Max. number of bus devices

Standard: 32 (= 1 bus segment)
With repeaters: 125

Max. cable length per bus
segment

1200 m (depending on the baud rate and cable type used)

External DC voltage supply

+24 V DC ±10 %, max. 100 mA

Operating conditions

Ambient conditions

Climate

Storage

IEC/EN 60721-3-1

1K3 (-25 to +60 °C)

Transport

IEC/EN 60721-3-2

2K3 (-25 to +70 °C)

Operation

Corresponding to the data of the Lenze standard device used (see
documentation of the standard device).

Pollution

EN 61800-5-1

Degree of pollution 2

Degree of
protection

IP20 (protection against accidental contact according to NEMA 250 type 1)