Electrical installation – Lenze E82ZAFPC201 User Manual

Page 65

Advertising
background image

Electrical installation

Assignment of the terminals

6

EDK82ZAFPC-201 DE/EN/FR 6.0

65

H2_BelegungAnschlKlemmen-INS_Klembesch

Terminal
X3.2/

Designation

Function / level

PES

Additional HF shield termination

A

T/R(A)

RS485 data line A

B

T/R(B)

RS485 data cable B

CN

CNTR

For function see PROFIBUS standard *)

Level during data transmission: CNTR = HIGH
(+5 V DC, reference: GND3)

VP

For function see PROFIBUS standard *)

U = +5 V DC (reference: GND3)
I

max

= 10 mA

40

GND3

Reference potential for PROFIBUS network *)

7

GND1

Reference potential for X3.1/20 and X3.2/20

39

GND2

Reference potential of the

digital inputs at X3.1/E1 and X3.1/E2
controller inhibit (CINH) at X3.2/28

28

CINH

Controller inhibit

Start = HIGH (+12 ... +30 V DC)
Stop = LOW (0 ... +3 V DC)
(reference: GND2)

20

DC voltage source for internal supply of controller inhibit (CINH)

+20 V DC (reference: GND1)
I

max

= 20 mA

59

External DC voltage supply for the function module

+24 V DC

±

10% (reference: GND1)

Current consumption on 24 V DC: 80 mA

The current for looping through the supply voltage to other nodes
via terminal 59 must be max. 3 A.

*) E.g. for repeater connection

Advertising