6

Electrical installation

Assignment of the terminals

EDK82ZAFPC-201 DE/EN/FR 6.0

64

H2_BelegungAnschlKlemmen-INS_Klembesch

Assignment of the terminals

Terminal
X3.1/

Designation

Function / level

E1

Digital inputs *)

Adapt the individual setting via C0007 or C0410.

Input resistance: 3.3 k

0 = LOW (0 ... +3 V DC) PLC level, HTL
1 = HIGH (+12 ... +30 V DC) PLC level, HTL
(reference: GND2)

E2

20

DC voltage source for the internal supply of the digital inputs E1 and
E2

+20 V DC (reference: GND1)
I

max

= 20 mA

39

GND2

Reference potential of the

digital inputs at X3.1/E1 and X3.1/E2
controller inhibit (CINH) at X3.2/28

59

External DC voltage supply for the function module

+24 V DC

±

10% (reference: GND1)

Current consumption on 24 V DC: 80 mA

The current for looping through the supply voltage to other nodes
via terminal 59 must be max. 3 A.

7

GND1

Reference potential for X3.1/20 and X3.2/20

*) Alternatively frequency input 0 ... 10 kHz (one-track) or 0 ... 1 kHz (two-track) configuration via C0425