Commissioning

Connecting the mains voltage

7

EDK82ZAFPC-201 DE/EN/FR 6.0

77

H2 NetzspgZuschalten-unkontroll_Anlauf_FIF

Connecting the mains voltage

Note!

If the external voltage supply of the function module is used, the supply must
be switched on as well.

ƒ The standard device will be ready for operation approx. 1 s after switching on the

supply voltage.

ƒ Controller inhibit is active.
ƒ The green LED at the front of the function module is lit (only visible in the case of the

8200 vector frequency inverter).

Protection against uncontrolled start-up

Note!

Establishing communication

For establishing communication via an externally supplied function module,
the standard device must be switched on as well.

ƒ

After communication has been established, the externally supplied module
is independent of the power on/off state of the standard device.

Protection against uncontrolled start-up

After a fault (e.g. short-term mains failure), a restart of the drive is not always
wanted and - in some cases - even not allowed.
The restart behaviour of the controller can be set in C0142:

ƒ

C0142 = 0 (Lenze setting)
– The controller remains inhibited (even if the fault is no longer active).
– The drive starts in a controlled mode by explicitly enabling the

controller: LOW-HIGH edge at terminal 28 (CINH)

ƒ

C0142 = 1
– An uncontrolled restart of the drive is possible.