Cable cross-sections and screw-tightening torques, 6electrical installation – Lenze E82ZAFPC201 User Manual
Page 66
Advertising
![background image](/manuals/565871/66/background.png)
6
Electrical installation
Cable cross-sections and screw-tightening torques
EDK82ZAFPC-201 DE/EN/FR 6.0
66
H2_LtgQuer+AnzMom-Klemmenleiste
Cable cross-sections and screw-tightening torques
Range
Values
Electrical connection
Terminal strip with screw connection
Possible connections
rigid:
1.5 mm
2
(AWG 16)
flexible:
without wire end ferrule
1.0 mm
2
(AWG 18)
with wire end ferrule, without plastic sleeve
0.5 mm
2
(AWG 20)
with wire end ferrule, with plastic sleeve
0.5 mm
2
(AWG 20)
Tightening torque
0.22 ... 0.25 Nm (1.9 ... 2.2 lb-in)
Bare end
5 mm