7commissioning – Lenze E82ZAFPC201 User Manual

Page 70

Advertising
background image

7

Commissioning

Commissioning steps

EDK82ZAFPC-201 DE/EN/FR 6.0

70

H2_Inbetriebnahmeschritte-Teil2MA

Step

Description

Detailed
information

9.

Use C1511 to assign the process data output words (POW) of the
master to the process data input words of the standard device.

Lenze setting:

POW1: DRIVECOM control word (DRIVECOM-CTRL)

POW2: Setpoint1 (NSET1-N1)

POW3: Setpoint2 (NSET1-N2)

POW4: Additional setpoint (PCTRL1-NADD)

POW5: Actual process controller value (PCTRL1-ACT)

POW6: Process controller setpoint (PCTRL1-SET1)

POW7: Reserved (FIF-RESERVED)

POW8: Torque setpoint or torque limit value (MCTRL1-MSET)

POW9: PWM voltage (MCTRL1-VOLT-ADD)

POW10: PWM angle (MCTRL1-PHI-ADD)

10.

Use C1510 to assign the process data output words of the standard
device to the process data input words (PIW) of the master.

Lenze setting:

PIW1: DRIVECOM status word (DRIVECOM STAT)

PIW2: Output frequency with slip (MCTRL1-NOUT+SLIP)

PIW3: Output frequency without slip (MCTRL1-NOUT)

PIW4: Apparent motor current (MCTRL1-IMOT)

PIW5: Actual process controller value (PCTRL1-ACT)

PIW6: Process controller setpoint (PCTRL1-SET1)

PIW7: Process controller output (PCTRL1-OUT)

PIW8: Controller load (MCTRL1-MOUT)

PIW9: DC-bus voltage (MCTRL1-DCVOLT)

PIW10: Ramp function generator input (NSET1-RFG1-IN)

11.

Enable process output data with C1512 = 65535.

Only required if C1511 has been changed.
Do not deactivate the process data words used by setting the
respective subcodes of code C1511 = 0.
The value in C1512 is volatile and all process data are enabled
after every switch-on.