Installation

Electrical installation

Voltage supply

5

l

27

EDSMF2192IB EN 3.1

5.2.5

Voltage supply

Internal voltage supply

)

Note!

Internal voltage supply has been selected in the case of standard devices with
an extended AIF interface opening (e.g. front of 8200 vector). The area shown
on a grey background in the graphic marks the jumper position.

ƒ

By default, this is not supplied internally in the standard device.

ƒ

For internal voltage supply place the jumper on the position indicated
below.

In the case of all other device series (9300, ECS), voltage is always supplied
from the standard device.

Lenze setting

(Only external voltage supply possible.)

Internal voltage supply

External voltage supply

)

Note!

Always use a separate power supply unit in every control cabinet and safely
separate it according to EN 61800−5−1 ("SELV"/"PELV") in the case of external
voltage supply and larger distances between the control cabinets.

The external voltage supply of the communication module ...

ƒ

is required if communication via the fieldbus is to be continued when the supply of
the device fails.

ƒ

is provided via the 2−pin terminal strip with screw−type connection (24 V DC):

Terminal

Description

+

External voltage supply
U = 24 V DC (20.4 V − 0 % ... 28.8 V + 0 %)
I = 85 mA

Reference potential for external voltage supply

ƒ

The parameters of a standard device disconnected from the mains cannot be
accessed.