Parameter data transfer – Lenze EMF2192IB User Manual

Page 45

Advertising
background image

Parameter data transfer

Reading and writing parameters

Reading parameters (expedited upload)

9

l

45

EDSMF2192IB EN 3.1

SDO Upload Expedited Response

An "SDO Upload Expedited Response" takes place if the data length of the parameter data
to be read amounts to up to 4 bytes.

Detailed breakdown of the data for an "SDO Upload Expedited Response":

SDO frame
area

Data field

Data type / length

Value / description

Mailbox Header

Length

WORD

2 bytes

0x0A: Length of the mailbox service data

Address

WORD

2 bytes

Station address of the source if an EtherCAT master is the instructing
party.
Station address of the target if an EtherCAT slave is the instructing
party.

Channel

WORD

6 bits (0 ... 5)

0x00: Reserved

Priority

2 bits (6, 7)

0x00: Lowest priority
...
0x03: Highest priority

Type

4 bits (8 ... 11)

0x03: CANopen over EtherCAT (CoE)

Reserved

4 bits (12 ... 15)

0x00

CANopen Header

Number

WORD

9 bits (0 ... 8)

0x00

Reserved

3 bits (9 ... 11)

0x00

Service

4 bits (12 ... 15)

0x03: SDO Response

SDO

Size indicator

BYTE

1 bit (0)

0x01: Size of the data in "data set size"

Transfer type

1 bit (1)

0x01: Expedited transfer

Data set size

2 bits (2, 3)

0x00: 4 bytes data
0x01: 3 bytes data
0x02: 2 bytes data
0x03: 1 byte data

Complete access

1 bit (4)

0x00: The entry addressed with index and subindex is read.
0x01: The complete object is read.

Command specifier

3 bits (5 ... 7)

0x02: Upload Response

Index

WORD

2 bytes

Index of the object

Subindex

BYTE

1 byte

Subindex of the object
0x00 or 0x01 if "complete access" = 0x01.

Data

DWORD

4 bytes

Data of the object