3 ethercat state machine, Ethercat state machine, Data transfer – Lenze EMF2192IB User Manual
Page 40
![background image](/manuals/565923/40/background.png)
Data transfer
EtherCAT state machine
l
40
EDSMF2192IB EN 3.1
7.3
EtherCAT state machine
Before communication via EtherCAT is possible, the fieldbus passes through the EtherCAT
status machine during power−up. The following illustration shows the possible state
changes from an EtherCAT slave view:
Operational
Pre-Operational
Init
Safe-Operational
E94AYCET009
Fig. 7−1
EtherCAT state machine
Status
Description
Init
l
Initialisation phase
l
No SDO/PDO communication with the slaves
l
The device detection is provided by a fieldbus scan.
Pre−operational
l
The fieldbus is active.
l
The SDO communication (mailbox communication) is possible.
l
No PDO communication
Safe−operational
l
The SDO communication (mailbox communication) is possible.
l
PDO communication:
– The input data is transmitted to the master and evaluated.
– The output data is the "Safe" status. They will not be transmitted to the standard
device.
Operational
l
Normal operation:
– SDO communication
– PDO communication
– Fieldbus synchronisation successful (if used)