4 technical data, General data, Operating conditions – Lenze E82ZAFUC001 User Manual
Page 48: Technical data, 4technical data
![background image](/manuals/565938/48/background.png)
4
Technical data
General data
EDK82ZAFUC−001 DE/EN/FR 4.0
48
l
H1_Daten−IP20
4
Technical data
General data
Field
Values
Order designation
E82ZAFUC001
Communication profile
CANopen, DS301 V4.02
Communication medium
DIN ISO 11898
Network topology
Line terminated at both ends with 120
W
resistor
Max. number of nodes
Max. 127 (with repeater)
Possible number of nodes per
segment
l
For E82ZAFUC001: 106 (max.)
l
In the case of different nodes:
see notes for mixed operation
^ 55
CANopen nodes
Slave
Baud rate [kbps]
10, 20, 50, 125, 250, 500, 1000
Process data words
1 ... 12 words
Operating conditions
Ambient conditions
Climate
Storage
IEC/EN 60721−3−1
1K3 (−25 to +60 °C)
Transport
IEC/EN 60721−3−2
2K3 (−25 to +70 °C)
Operation
Corresponding to the data of the Lenze standard device used (see
documentation of the standard device).
Pollution
EN 61800−5−1
Degree of pollution 2
Degree of protection
IP20 (protection against accidental contact according to NEMA 250 type 1)