7

Commissioning

Setting node address and baud rate

EDK82ZAFUC−001 DE/EN/FR 4.0

66

l

H2_set_node_addr_baud−Ueb−rate Hinweis

Setting node address and baud rate

)

Note!

Node address and baud rate can be set via DIP switches or codes.

ƒ

Select an unambiguous node address between 1 and 63 for each device.

ƒ

The baud rate must be set to the same value for all controllers and the
master computer.

ƒ

If the DIP switches S1 ... S7 are in OFF position, the code settings for node
address/baud rate are active. If a DIP switch is set to ON, the node address
(C1509)/baud rate (C1516) will be overwritten with the corresponding
values of the switch positions.

Settings via codes

ƒ

DIP switches S1 ... S7 = OFF (Lenze setting)

ƒ

Set the node address via C1509.

ƒ

Set the baud rate via C1516.

Settings via the DIP switches at the front

ƒ

Set the node address via DIP switches S1 ... S7.

ƒ

Set the baud rate via DIP switches S8 ... S10.

Accepting changed settings

ƒ

Switch off the voltage supply of the function module and the controller
and then switch it on again to activate the changed settings.