Electrical installation
Bus cable length
EDK82ZAFUC−001 DE/EN/FR 4.0
54
l
H2 BusLeitgsLaenge−Leitungslaenge_3
Bus cable length
)
Note!
It is absolutely necessary to comply with the permissible cable lengths!
1. Check the compliance with the total cable length in Tab. 1.
The total cable length is defined by the baud rate.
Baud rate [kbps]
Total cable length [m]
10
8000
20
3900
50
1500
125
630
250
290
500
120
1000
25
Tab. 1
Total cable length
2. Check the compliance with the segment cable length in Tab. 2.
The segment cable length is defined by the cable cross−section used and by the number of
nodes per segment. Without a repeater the segment cable length corresponds to the total
cable length.
Max. number of
nodes per
segment
Cable cross−section
0.25 mm
2
0.5 mm
2
0.75 mm
2
1.0 mm
2
2
240 m
430 m
650 m
940 m
5
230 m
420 m
640 m
920 m
10
230 m
410 m
620 m
900 m
20
210 m
390 m
580 m
850 m
32
200 m
360 m
550 m
800 m
63
170 m
310 m
470 m
690 m
100
150 m
270 m
410 m
600 m
Tab. 2
Segment cable length