Bus cable length, 6electrical installation – Lenze E82ZAFUC001 User Manual

Page 54

Advertising
background image

6

Electrical installation

Bus cable length

EDK82ZAFUC−001 DE/EN/FR 4.0

54

l

H2 BusLeitgsLaenge−Leitungslaenge_3

Bus cable length

)

Note!

It is absolutely necessary to comply with the permissible cable lengths!

1. Check the compliance with the total cable length in Tab. 1.

The total cable length is defined by the baud rate.

Baud rate [kbps]

Total cable length [m]

10

8000

20

3900

50

1500

125

630

250

290

500

120

1000

25

Tab. 1

Total cable length

2. Check the compliance with the segment cable length in Tab. 2.

The segment cable length is defined by the cable cross−section used and by the number of
nodes per segment. Without a repeater the segment cable length corresponds to the total
cable length.

Max. number of
nodes per
segment

Cable cross−section

0.25 mm

2

0.5 mm

2

0.75 mm

2

1.0 mm

2

2

240 m

430 m

650 m

940 m

5

230 m

420 m

640 m

920 m

10

230 m

410 m

620 m

900 m

20

210 m

390 m

580 m

850 m

32

200 m

360 m

550 m

800 m

63

170 m

310 m

470 m

690 m

100

150 m

270 m

410 m

600 m

Tab. 2

Segment cable length

Advertising