Wiring to a host, Electrical installation – Lenze E82ZAFUC001 User Manual

Page 53

Advertising
background image

Electrical installation

Wiring to a host

6

EDK82ZAFUC−001 DE/EN/FR 4.0

53

l

H2 VerdrahtLeitrechner−leitungsspez

Wiring to a host

The following illustration shows the CAN cable routing on the function module:

CG

CG

GND

8200 vector

8200 vector

SPS/PC

E82ZAFUC001

E82ZAFUC001

120

120

CL

CL

LOW

CH

CH

HIGH

+

+

+

E82ZAFU014

Frequency inverters of the 8200 vector/motec series with plugged−in function modules
communicate with the CANopen master via CANopen.

Specification of the transmission cable

We recommend the use of CAN cables in accordance with ISO 11898−2:

CAN cable in accordance with ISO 11898−2

Cable type

Paired with shielding

Impedance

120

W

(95 ... 140

W

)

Cable resistance / cross−section

Cable length

£

300 m

£

70 m

W

/m / 0.25 … 0.34 mm

2

(AWG22)

Cable length 301 … 1000 m

£

40 m

W

/m / 0.5 mm

2

(AWG20)

Signal propagation delay

£

5 ns/m