Electrical installation
Wiring to a host
EDK82ZAFUC−001 DE/EN/FR 4.0
53
l
H2 VerdrahtLeitrechner−leitungsspez
Wiring to a host
The following illustration shows the CAN cable routing on the function module:
CG
CG
GND
8200 vector
8200 vector
SPS/PC
E82ZAFUC001
E82ZAFUC001
120
120
CL
CL
LOW
CH
CH
HIGH
+
+
+
E82ZAFU014
Frequency inverters of the 8200 vector/motec series with plugged−in function modules
communicate with the CANopen master via CANopen.
Specification of the transmission cable
We recommend the use of CAN cables in accordance with ISO 11898−2:
CAN cable in accordance with ISO 11898−2
Cable type
Paired with shielding
Impedance
120
W
(95 ... 140
W
)
Cable resistance / cross−section
Cable length
£
300 m
£
70 m
W
/m / 0.25 0.34 mm
2
(AWG22)
Cable length 301 1000 m
£
40 m
W
/m / 0.5 mm
2
(AWG20)
Signal propagation delay
£
5 ns/m