Assignment of the terminals

6

EDK82ZAFUC−001 DE/EN/FR 4.0

59

l

H2_BelegungAnschlKlemmen−klemmbesch−001

Assignment of the terminals

Terminal

X3/

Designation

Function / level

CG

CAN−GND

Reference potential for CAN

CL

CAN−LOW

CAN data line (LOW)

CH

CAN−HIGH

CAN data line (HIGH)

59

External DC voltage supply for the function module:

l

24 V DC (21.4 V DC − 0 % ... 28.8 V DC + 0 %)

l

Current consumption at 24 V DC: 80 mA

The current flowing to other nodes via clamp 59 when looping
through the supply voltage must not exceed 3 A.

7

GND1

Reference potential for X3/20 and X3/59

39

GND2

Reference potential of controller inhibit (CINH) at X3/28

28

CINH

Controller inhibit

l

Input resistance: 3.3 k

W

l

Start = HIGH (+12 ... +30 V DC)

l

Stop = LOW (0 ... +3 V DC)
(reference: GND2)

20

DC voltage source for the external supply of controller inhibit (CINH)

l

+20 V DC (reference: GND1)

l

I

max

= 10 mA