Technical data

General data and operating conditions

4

l

49

EDK10200EV3 DE/EN/FR 7.1

4

Technical data

General data and operating conditions

Field

Values

Conformity

CE

Low−Voltage Directive (2006/95/EC)

Approvals

UL 508C

Underwriter Laboratories (File−No. E132659)
Power Conversion Equipment

DC supply voltage

Voltage

+18 VDC − 0 % ... +30 VDC + 0 %

Current

Max. 4.2 A at 24 VDC:

l

200 mA at +24 V (Drive PLC supply)

l

max. 1A per output at Drive PLC

Note: The outputs of the extension boards must be
supplied externally

Supply conditions

The device must not be connected to voltages > 50 V against PE.
The device must not be used in mains circuits.

Climatic conditions

Class 3K3 to EN 50178
(without condensation, average relative humidity 85 %)

Temperature range

Transport

−25 °C ... +70 °C

Storage

−25 °C ... +60 °C

Operation

0 °C ... +40 °C without power derating
+40 °C ... +55 °C with derating

Power derating

Of output currents at t

a

> +40 °C: 2.5 %/K

Vibration resistance

Resistant to acceleration up to 0.7 g

Permissible mounting
positions

Vertical

Free space

³ 100 mm below and above

Enclosure

IP 20

Total insulation

The degree of insulation of the device depends on the degree of
insulation of the voltage source and the components connected.