Electrical installation

Wiring of the system bus (CAN)

6

l

63

EDK10200EV3 DE/EN/FR 7.1

Wiring of the system bus (CAN)

(

Stop!

Only connect terminals of the same designation.

PES

PES

PES

GND LOW

HI

7 LO HI

7 LO HI

7 LO HI

7 LO HI

120

Ω

120

Ω

0

1

Drive PLC

plc014

0

Controller 1

1

Controller 2

PES

HF shield termination through PE connection

Features of the system cable:

Total cable length

up to 300 m

300 to 1000 m

Cable type

LIYCY 2 x 2 x 0.5 mm

2

CYPIMF 2 x 2 x 0.5 mm

2

Twisted pair with shielding
Pair 1: CAN−LOW (LO) and CAN−HIGH (HI)
Pair 2: 2 GND

Cable resistance

£40 W/km

£40 W/km

Capacitance per unit length

£130 nF/km

£60 nF/km