Terminal strips on the bottom of the device, Electrical installation – Lenze EPL1020x−EI User Manual
Page 61
Advertising
Electrical installation
Terminal strips on the bottom of the device
l
61
EDK10200EV3 DE/EN/FR 7.1
Terminal strips on the bottom of the device
plc003
Terminal Use
Level
Data
Analog
inputs
X4/AI1
Freely assignable input 1
−10 V ... +10 V
Resolution: 10 bits + sign
X4/AI2
Freely assignable input 2
X4/AI3
Freely assignable input 3
Analog
outputs
X4/AOV
Voltage output
−10 V ... +10 V /
max. 2 mA
Resolution: 10 bits + sign
Accuracy: ±0.5 %
X4/AOI
Current output
−20 mA ... +20 mA
X4/A
⊥
Ground for analog inputs
and outputs
−
−
System
bus (CAN)
X5/GND
CAN−GND
Reference potential
−
X5/LOW
CAN−LOW
System bus LOW
(data cable)
−
X5/HI
CAN−HIGH
System bus HIGH
(data cable)
−