Maloperation of the drive plc, Troubleshooting and fault elimination – Lenze EPL1020x−EI User Manual

Page 69

Advertising
background image

Troubleshooting and fault elimination

Maloperation of the Drive PLC

8

l

69

EDK10200EV3 DE/EN/FR 7.1

Maloperation of the Drive PLC

Maloperation

Cause

Remedy

Communication error
Log−in not possible

Drive PLC without supply voltage

Switch on the supply voltage

No connection between PC and
Drive PLC

Check wiring of system bus
^ Instructions for the PC system bus
module 2173IB

^

61

PC system bus module 2173IB is not
supplied with voltage
(LED at the PC system bus module is
off)

Plug in the voltage adapter for
DIN/PS2 keyboard connection
^ Instructions for the PC system bus
module 2173IB

No terminating resistor (120

W) in

the system bus

^

57

PC system bus module 2173IB has
not been initialised

Observe switch−on sequence:
1. Plug PC system bus module

2173IB on LPT1 or LPTx

2. Switch on PC

Faulty communication parameters

Set communication parameters
correctly
^ DDS Getting started",
chapter 4.4.2

PC does not respond
anymore

The system bus module has been
removed from the parallel prot (LPT)
of the PC during operation

Restart PC

A print job has been sent to the
interface used by the system bus
module

Restart PC and use another parallel
port (LPT) for printing

No control signal at digital
outputs (X2)

Missing connection between X1/+24
and X1/O24

Establish connection

^

59

Signals are not read in at
digital inputs (X3)

HIGH levels of the input signals are
too low (<13 V)

HIGH levels of the input signals must
amount to 13 V … 30 V

^

59