Drive system on the mains, Electrical isolation, Electrical installation – Lenze ECSDExxx User Manual

Page 83

Advertising
background image

Electrical installation

Drive system on the mains

Electrical isolation

4

l

83

EDKCSDE040 DE/EN/FR 4.0

4.2

Drive system on the mains

This information applies to the ECS drive system, consisting of:

ƒ

ECSxE... power supply module

ƒ

ECSxK series capacitor module (optional)

ƒ

ECSxS/P/M/A series axis module

ƒ

Motor

ƒ

Accessories

ƒ

Wiring

4.2.1

Electrical isolation

The integrated electrical isolation between the power section and the control
section is a protective separation (reinforced insulation) acc. to EN 61800−5−1.
To maintain this protective separation, it must be ensured that the external
24 V supply and all components connected to this supply also have a protective
separation (SELV/PELV) acc. to EN 61800−5−1.

24 V supply

DC bus

X6/+24, GND

X22

Basic
insulation
(50 V)

Dig. input/output

X6/DI1, DI2, D24, DO1

Reinforced
insulation
(300 V)

Thermostat

X6/T1, T2

CAN

X4

Mains

AIF

X21

X1

Fig. 4−1

Electrical isolation