Electrical installation

Power terminals

Connection to the DC bus (+U

G

, −U

G

)

4

l

91

EDKCSDE040 DE/EN/FR 4.0

4.3.2

Connection to the DC bus (+U

G

, −U

G

)

(

Stop!

ƒ

The supply of Lenze controllers of the 82xx and 93xx series is not
permitted.

ƒ

If synchronous motors with a high centrifugal mass are used, a
considerable amount of energy can be fed back into the DC bus.
Please take this into account when dimensioning the brake
resistor.

ƒ

If the total cable length is > 20 m, install an axis module or a capacitor
module directly at the power supply module.

ƒ

Design the ±U

G

cables twisted and as short as possible. Ensure

short−circuit−proof routing!

ƒ

Cable length (module

« module) > 30 cm: install shielded ±U

G

cables.

,

Documentation of the ECSxS/P/M/A axis modules

Observe the enclosed notes.

,

Documentation of the ECSxK capacitor module

Observe the enclosed notes.

Fuses
Fusing the DC−bus interconnection is not required if power supply modules of
the ECS series are used which are fused on the mains side.