Technical data – Lenze 8210 series User Manual

Page 13

Advertising
background image

Technical Data

UONu_^MPMQ

3-3

L

8214

8213

8212

8211

Type

150 % overload

EVF8214-E

EVF8213-E

EVF8212-E

EVF8211-E

Order no.

Motor voltage

3)

V

motor

[V]

0 - 3 × V

mains

/ 0Hz

¼ 50Hz, if required up to 480Hz

Power loss (operation with I

Nx

)

P

loss

[W]

55

75

90

100

Power reduction

[%/K]

[%/m]

40

°C < T

amb

< 50

°C: 2.5%/K

1000 m a.m.s.l < h ≤ 4000 m a.m.s.l: 5%/1000 m

Field

f

Resolution

Absolute

0.02 Hz

Field

frequency Digital setpoint

selection

Accuracy

0.05 Hz

Analog setpoint

l ti

Linearity

0.5 % (max. selected signal level: 5 V or 10 V)

Analog setpoint

selection

Temperature

sensitivity

0

¼ 40 °C: +0.4 %

Offset

0 %

Weight

m [kg]

2.2

2.2

2.2

2.2

Printed in bold Data for the operation with factory setting and a chopper frequency of 8 kHz.

1)

This power can be additionally obtained when operating a matching motor

2)

The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here
and 2 minutes base load with 75% I

Nx

.

3)

With mains choke/mains filter: max. output voltage = approx. 96 % of the mains voltage

*

Chopper frequency of the inverter

Show/Hide Bookmarks

Advertising